The text

(1) Except as permitted in Sentence (3), a spill of flammable liquids or combustible liquids shall be prevented from flowing outside the spill area and from reaching waterways, sewer systems and potable water sources by (a) constructing a noncombustible barrier capable of containing the spill, or (b) grading the site or sloping the floor to divert the spill to a drainage system conforming to Article 4.1.6.2. (2) When barriers required in Sentence (1) are provided to contain accidental spillage from aboveground storage tanks, they shall conform to the requirements for secondary containment in Subsection 4.3.7. (3) Water-miscible effluent from spills and firefighting operations is permitted to be directed into a sewer system provided it does not create a fire hazard or any risk to public health or safety. (4) Aboveground storage tanks shall be provided with a spill containment device as required by Sentences 4.3.6.4.(4) and 4.3.15.1.(3). Drainage systems
Read the fire code on e-Laws ↗