The text

(1) Except as permitted in Sentences (2) and (3), in dwelling units as described in Article 4.2.4.5. and in mercantile occupancies as described in Sentence 4.2.5.3.(3), Class I liquids shall not be stored, handled or used in basements or pits. (2) Up to 10 L of Class I liquid is permitted to be stored in basements, provided it is stored in safety containers conforming to ULC/ORD-C30, “Safety Containers”. (3) Laboratories in basements may store, handle or use flammable liquids and combustible liquids if the laboratories meet the requirements of Article 5.5.6.2. Maintenance