The text
(1) Except as provided in Article 4.1.2.2., for the purposes of this Part, flammable liquids and combustible liquids shall be classified in conformance with Sentences (2) and (3).
(2) Flammable liquids shall be Class I liquids and shall be subdivided into:
(a) Class IA liquids, which shall include those having a flash point below 22.8°C and a boiling point below 37.8°C,
(b) Class IB liquids, which shall include those having a flash point below 22.8°C and a boiling point at or above 37.8°C, and
(c) Class IC liquids, which shall include those having a flash point at or above 22.8°C and below 37.8°C.
(3) Combustible liquids shall be Class II or Class IIIA liquids and shall be subdivided into:
Class II liquids, which shall include those having a flash point at or above 37.8°C and below 60°C, and
Class IIIA liquids, which shall include those having a flash point at or above 60°C and below 93.3°C.
Water-miscible liquid mixtures