fire code, O. Reg. 213/07

Section 3.3.2.12

Cite as fire code, O. Reg. 213/07, s. 3.3.2.12 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Unless otherwise approved, each storage yard shall be provided with at least two fire access routes in conformance with Sentence (2). (2) The fire access routes required in Sentence (1) shall (a) have a clear width of at least 6 m, unless it can be shown that lesser widths are satisfactory, (b) be designed to support the expected loads imposed by fire fighting equipment and be surfaced with concrete, asphalt or other material designed to permit accessibility under all climatic conditions, (c) be connected with a public thoroughfare, and (d) be located as remotely as is possible in the circumstances from each other.