fire code, O. Reg. 213/07
Section 3.2.7.9
Cite as fire code, O. Reg. 213/07, s. 3.2.7.9 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as permitted in Sentences (2) and (3) and in Part 4, buildings used for the storage of dangerous goods regulated by this Subsection shall be equipped throughout with a
(a) sprinkler system designed in conformance with Article NFPA 13, “Standard for the Installation of Sprinkler Systems”, or
(b) fire suppression system designed in conformance with Article 2.1.3.5.
(2) Buildings described in Sentence (1) need not be equipped throughout with a sprinkler system or other fire suppression system provided that
(a) the sum of individual storage areas in the building used for the storage of dangerous goods, other than substances classified as miscellaneous dangerous goods with no other class and those covered in Part 4, does not exceed 100 m2, and
(b) the dangerous goods are
(i) separated in conformance with Table 3.2.7.6., and
(ii) stored in fire compartments separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h.
(3) Buildings described in Sentence (1) need not be equipped throughout with a sprinkler system or other fire suppression system, provided that storage consists only of dangerous goods classified as non-flammable, non-toxic gases with no subsidiary class of oxidizing substances.
Smoke venting
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.