fire code, O. Reg. 213/07
Section 3.2.7.12
Cite as fire code, O. Reg. 213/07, s. 3.2.7.12 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentences (2) and (3), fire department access to buildings described in Article 3.2.7.1. shall be in conformance with Section 2.5.
(2) When the collective individual storage area for dangerous goods exceeds 10 m2, buildings regulated by Sentence (1) shall be accessible to fire department vehicles from at least two sides for the purpose of firefighting.
(3) In buildings regulated by Sentence (1), access openings to each storey provided in conformance with the Building Code shall be not less than 750 mm wide by 1100 mm high.
Labels
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.