fire code, O. Reg. 213/07

Section 3.2.5.8

Cite as fire code, O. Reg. 213/07, s. 3.2.5.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentence (2), the height of storage of packaged Level 2 or 3 aerosols shall be not greater than (a) 1.75 m where products are in solid piles or on pallets, or (b) 6.1 m where products are on racks. (2) Where the building is sprinklered in conformance with Article 3.2.5.5. and an enclosure conforming to Article 3.2.5.6. or 3.2.5.7. is provided, the height of storage of packaged Level 2 or 3 aerosols shall be not greater than (a) 6.1 m where products are in solid piles or on pallets, or (b) the height limit determined by the design capacity of the sprinkler system where products are on racks. Aisles
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.