fire code, O. Reg. 213/07

Section 3.2.4.4

Cite as fire code, O. Reg. 213/07, s. 3.2.4.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Baled combustible fibres shall be stored so that (a) a single pile will not contain more than 700 m3, (b) the maximum height of any single pile will not exceed 4.5 m, (c) piles are separated by aisles not less than 1.5 m wide, and (d) the clearance between piles and building walls is not less than 1 m. Baled storage piles
Read the fire code on e-Laws ↗