The text
(1) Individual storage areas of bagged ammonium nitrate shall not exceed 1500 m2 in area and 9 m in height.
(2) Wall clearances of not less than 600 mm shall be maintained where stored products may swell or expand with the absorption of water.
(3) In buildings that are not sprinklered, a clearance of not less than 1 m between the top of storage and the underside of the floor or roof deck shall be maintained.
(4) The clearance between the top of storage and ceiling sprinkler deflectors shall conform to the standard used to design the sprinkler system.
(5) Ammonium nitrate shall not be stored in an area where the ambient temperature is such that it can become unstable or susceptible to undesirable reactions.
(6) Ammonium nitrate storage shall be identified by signs of contrasting colours indicating the contents with letters 50 mm high.
(7) Bulk storage of ammonium nitrate shall be located indoors or in enclosed bin-type structures.
(8) Bins used for the storage of ammonium nitrate shall not contain galvanized iron, copper, lead or zinc or other materials that may contaminate or be corroded by ammonium nitrate.
Automatic sprinklers
Read the fire code on e-Laws ↗