fire code, O. Reg. 213/07
Section 3.2.3.2
Cite as fire code, O. Reg. 213/07, s. 3.2.3.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A building used for the storage of ammonium nitrate shall not be more than 1 storey in building height.
(2) A building used for the storage of ammonium nitrate shall not
(a) have basements or crawl spaces, or
(b) contain open floor drains, tunnels, elevator pits or other pockets which might trap molten ammonium nitrate.
(3) A building used for the storage of ammonium nitrate shall have not less than 70 cm2 in vent area for each square metre of storage area unless mechanical ventilation is provided.
(4) All flooring in storage areas shall be of noncombustible materials.
(5) A building used for the bulk storage of ammonium nitrate shall be designed to prevent contact with building material that
(a) will cause the ammonium nitrate to become unstable,
(b) may corrode or deteriorate by reason of contact with the ammonium nitrate, or
(c) will become impregnated by ammonium nitrate.
(6) The distance between an ammonium nitrate storage facility and the property line of another property shall be not less than
(a) 15 m where the other property contains a warehouse for flammable liquids storage or a facility for loading or unloading flammable liquids,
(b) 15 m where the other property contains a building classified as medium-hazard industrial occupancy or low-hazard industrial occupancy provided the ammonium nitrate storage facility does not exceed 200 t of ammonium nitrate,
(c) 30 m where the other property contains a building classified as industrial occupancy not covered in Clause (b), flammable liquids storage tanks, flammable gas storage tanks or other tanks containing a hazardous substance, or
(d) 90 m for all other occupancies.
(7) The distance in Clause (6)(b) may be reduced to 7.5 m if a firewall that has a fire-resistance rating not less than 2 h is provided between the storage facility and the building it exposes.
(8) The distance in Clause (6)(c) may be reduced to 15 m for a medium-hazard industrial occupancy or a low-hazard industrial occupancy if a firewall that has a fire-resistance rating not less than 2 h is provided between the storage facility and the building it exposes.
(9) The use of buildings or structures that do not conform with the provisions of Sentences (6) to (8) may be approved where the buildings or structures do not constitute a hazard to life or property from fire or explosion.
(10) Except where other forms of exposure protection are approved, the walls of the exposed side of a storage building shall be noncombustible where such walls are within 15 m of a
(a) combustible building,
(b) forest, or
(c) pile of combustible material.