fire code, O. Reg. 213/07

Section 3.2.2.6

Cite as fire code, O. Reg. 213/07, s. 3.2.2.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Adequate access for fire fighting purposes shall be provided and maintained to all portions of the premises, in conformance with Sentences (2) to (6). (2) Access aisles not less than 1.0 m wide shall be provided to exits, to fire department access panels and to fire protection equipment. (3) Aisles shall be maintained free of obstruction. (4) Except as permitted by Sentence (5), at least one main access aisle shall extend the length of the building with a minimum width of (a) 2.4 m for storage heights not more than 6 m, and (b) 3.6 m for storage heights of more than 6 m. (5) Narrower aisles may be approved where the building is sprinklered and the sprinkler design is based on aisle widths less than required by Sentence (4) but in no case shall the aisle width be less than the aisle width on which the sprinkler design is based. (6) In storage areas that exceed 200 m2, main access aisles referred to in Sentence (4) shall be accessible from at least two fire department access points, which shall be located such that, in the event one becomes unusable due to fire, the other will still allow emergency responders to access the building.
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.