fire code, O. Reg. 213/07
Section 3.2.1.10
Cite as fire code, O. Reg. 213/07, s. 3.2.1.10 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) In addition to the requirements of Section 6.2, multi-purpose dry chemical portable extinguishers having a rating of 4A:80B shall be installed
(a) in every 500 m2 of floor area, and
(b) so that the distance travelled to any extinguisher does not exceed 25 m.
Subsection 3.2.2. Indoor General Storage
Application
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.