The text

(1) Indoor public amusement areas that involve enclosed, confined or otherwise confusing configurations shall be provided with emergency egress points that (a) have appropriate width, height and capacity for the anticipated occupant load, (b) are not more than 15 m travel from any point within the public amusement area except as approved, (c) are clearly identified with signs, and (d) are equipped with emergency lighting providing a minimum lighting level of 10 lx at floor or pathway level for a duration of at least 30 min, where natural lighting is not sufficient in the circumstances. SECTION 2.8 EMERGENCY PLANNING Subsection 2.8.1. General Application
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.