fire code, O. Reg. 213/07
Section 2.7.2.2
Cite as fire code, O. Reg. 213/07, s. 2.7.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Subject to Sentences (2) and (3), and unless otherwise approved, locking, latching and other fastening devices shall be such that a door can be readily opened from the inside with no more than one releasing operation and without requiring keys, special devices or specialized knowledge of the door opening mechanism on
(a) every exit door, and
(b) every door that is in an access to exit and that opens into or is located within
(i) a public corridor,
(ii) a facility that provides access to exit from a suite,
(iii) a facility that provides access to exit from a room serving patients or residents in a care occupancy, care and treatment occupancy or retirement home, or
(iv) a floor area, or portion of a floor area, that contains a hazardous extraction operation.
(2) A door in an access to exit or an exit door may be equipped with an electromagnetic locking device that is approved or complies with the Building Code, unless the door is located in an elementary or secondary school or is an egress or exit door that serves a high-hazard industrial occupancy.
(3) An egress door that serves a contained use area or impeded egress zone may be equipped with a locking device that can be released either locally or remotely in accordance with Sentences (4) to (6).
(4) A locking device with a local release permitted by Sentence (3) shall be capable of being unlocked with a key from both sides of the door.
(5) The controls for the remote release of a locking device permitted by Sentence (3) shall be in an area that is readily accessible to supervisory staff.
(6) A locking device permitted by Sentence (3) that is electrically operated shall be
(a) designed to operate on emergency power, and
(b) capable of being manually unlocked by supervisory staff.
(7) Sentence (1) does not apply in rapid transit stations that comply with the Building Code or to agricultural occupancies with no human occupants.
Egress doors
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.