fire code, O. Reg. 213/07
Section 2.7.1.1
Cite as fire code, O. Reg. 213/07, s. 2.7.1.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Aisles in conformance with Sentences (2) to (4) shall be provided in every floor area in a mercantile occupancy and a business and personal services occupancy, and in a floor area or portion of a floor area containing a hazardous extraction operation, that
(a) is not subdivided into rooms or suites served by corridors giving access to exits, and
(b) is required to have more than one exit.
(2) Every required exit shall be served by an aisle that
(a) has a clear width not less than 1100 mm,
(b) has access to at least one additional exit, and
(c) at every point in the aisle provides a choice of two directions by which to reach an exit.
(3) A subsidiary aisle with only a single direction of travel to an aisle described in Sentence (2) is permitted if it has a clear width not less than 900 mm and a length that is not greater than 7.5 m.
(4) Every individual work area in a business and personal services occupancy shall be located adjacent to an aisle or subsidiary aisle.
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.