fire code, O. Reg. 213/07

Section 2.4.1.2

Cite as fire code, O. Reg. 213/07, s. 2.4.1.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Corridors serving as access to exits for guest suites may contain solid wood or other approved furniture, provided the furniture does not create an obstruction to the egress route. (2) For the purpose of Sentence (3), “furniture” means (a) seating, (b) tables, or (c) cabinets for displaying decorative objects. (3) Corridors or lobbies serving as access to exits in residential occupancies, including retirement homes or care occupancies, may contain furniture, provided the furniture does not create an obstruction to the egress route and (a) the furniture is non-combustible, (b) the furniture is constructed of solid wood, (c) furniture is placed in groupings of no larger than 4.6 m2, with each grouping separated from any other grouping by a minimum of 3 m and (i) is in a corridor or lobby that is sprinklered, and (ii) is in a corridor or lobby equipped with smoke detectors as part of the building fire alarm system or equipped with smoke alarms installed in accordance with Sentences 2.13.2.1.(2) and (3) in the vicinity of the furniture area if the building does not have a fire alarm system, or (d) the furniture is approved. (4) Sentence (3) does not apply to corridors described in Sentence (1). Waste receptacles
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.