fire code, O. Reg. 213/07

Section 2.16.2.1

Cite as fire code, O. Reg. 213/07, s. 2.16.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Where a fuel-burning appliance, flue or a fireplace is installed in a suite of residential occupancy or care occupancy, a carbon monoxide alarm shall be installed (a) adjacent to each sleeping area in the suite, and (b) on each storey without a sleeping area in the suite. (2) Where a fuel-burning appliance is installed in a building, but not within a suite of residential occupancy or care occupancy, a carbon monoxide alarm shall be installed (a) in the service room or area where the appliance is installed, (b) adjacent to each sleeping area within each suite of residential occupancy or care occupancy where the suite has a common wall or common floor/ceiling assembly with the service room or area where the appliance or flue is installed, (c) on each storey without a sleeping area within each suite of residential occupancy or care occupancy where the suite has a common wall or common floor/ceiling assembly with the service room or area where the appliance or flue is installed, and (d) adjacent to each sleeping room that is not within a dwelling unit. (3) Where a building contains a storage garage, a carbon monoxide alarm shall be installed (a) adjacent to each sleeping area within each suite of residential occupancy or care occupancy where the suite has a common wall or common floor/ceiling assembly with the storage garage, (b) on each storey without a sleeping area within each suite of residential occupancy or care occupancy where the suite has a common wall or common floor/ceiling assembly with the storage garage, and (c) adjacent to each sleeping room that is not within a dwelling unit. (4) Where a forced-air fuel-burning appliance provides heated air to a building but is not located within a suite of residential occupancy or care occupancy, a carbon monoxide alarm shall be installed (a) in the service room or area where the appliance is installed, if the appliance is located in the building, (b) in public corridors serving suites of residential occupancy where the corridor is directly heated by the forced-air fuel burning appliance including (i) at least one carbon monoxide alarm in each portion of a divided corridor, and (ii) each carbon monoxide alarm in an undivided portion of a corridor is spaced not more than 25 m apart, (c) adjacent to each sleeping area within each suite of residential occupancy or care occupancy directly heated by the forced-air fuel burning appliance, and (d) on each storey without a sleeping area within each suite of residential occupancy or care occupancy directly heated by the forced-air fuel burning appliance. (5) A carbon monoxide alarm shall (a) be permanently connected to an electrical circuit with no disconnect switch between the overcurrent device and the carbon monoxide alarm, (b) be battery-operated, or (c) be plugged into an electrical receptacle. (6) A carbon monoxide alarm shall meet the requirements of CSA-6.19, “Residential Carbon Monoxide Alarming Devices” or UL 2034, “Single and Multiple Station Carbon Monoxide Alarms”. (7) A carbon monoxide alarm shall be mechanically fixed, attached, plugged in or placed at the manufacturer’s recommended height or, if the manufacturer has not recommended a height, on or near the ceiling. (8) A carbon monoxide alarm that is installed adjacent to a sleeping area shall be equipped with an alarm that is audible throughout the sleeping area, even if any doors between the carbon monoxide alarm and any parts of the sleeping area are closed. Section 2.17 Farm Buildings Subsection 2.17.1. Fire Hazards and Control Electrical systems
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.