fire code, O. Reg. 213/07
Section 2.13.2.1
Cite as fire code, O. Reg. 213/07, s. 2.13.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A smoke alarm shall be installed
(a) if a sleeping area in a dwelling unit is served by a hallway, in the hallway,
(b) if a sleeping area in a dwelling unit is not served by a hallway, between the sleeping area and the remainder of the dwelling unit,
(c) if a sleeping room is not within a dwelling unit, in the sleeping room, and
(d) on each storey without a sleeping area in a dwelling unit.
(2) A smoke alarm shall
(a) be permanently connected to an electrical circuit with no disconnect switch between the overcurrent device and the smoke alarm, or
(b) be battery-operated.
(3) A smoke alarm shall meet the requirements of CAN/ULC-S531, “Standard for Smoke Alarms”.
(4) Smoke detectors forming part of a residential fire warning system installed in conformance with CAN/ULC-S540, “Standard for Residential Fire and Life Safety Warning Systems: Installation, Inspection, Testing and Maintenance” and in conformance with the residential fire warning system provisions in Part 9 of Division B of the Building Code are deemed to be in compliance with Sentences (2) and (3).