drinking water systems, O. Reg. 170/03
Schedule 15.1
Cite as drinking water systems, O. Reg. 170/03, Schedule 15.1 · current to November 11, 2026 · consolidated from April 11, 2022 · read from e-Laws on November 16, 2026
The text
SCHEDULE 15.1 LEAD
Municipal: Large Residential Small Residential
Non-Municipal: Year-Round Residential
Application
15.1-1. This Schedule applies to the following drinking water systems:
1. Large municipal residential systems.
2. Small municipal residential systems.
3. Non-municipal year-round residential systems.
Limited meaning of “serve”
15.1-2. For the purposes of this Schedule,
(a) a drinking water system serves a population if its distribution system is directly connected to the plumbing that serves the population;
(b) a drinking water system serves a private residence or other building if its distribution system is directly connected to the plumbing that serves the private residence or other building.
Definitions
15.1-3. In this Schedule,
“lead plumbing” and “lead service pipes” mean plumbing and service pipes with a lead content greater than 8 per cent; (“installation de plomberie en plomb”, “conduites de branchement en plomb”)
“lead solder” means solder with a lead content greater than 0.2 per cent; (“soudures de plomb”)
“Schedule 2 standard” means a standard prescribed for any substance in Schedule 2 to the Ontario Drinking Water Quality Standards; (“norme prescrite à l’annexe 2”)
“standard prescribed for lead” means the standard prescribed for lead in Schedule 2 to the Ontario Drinking Water Quality Standards; (“norme prescrite à l’égard du plomb”)
Standard sampling
15.1-4. (1) The owner of a drinking water system and the operating authority for the system shall ensure that, in accordance with sections 15.1-6 and 15.1-7, samples are taken during the periods described in subsection (2),
(a) in plumbing that serves private residences, from at least the number of points set out in Column 3 of the Table to this section opposite the population served by the drinking water system;
(b) in plumbing that does not serve private residences, from at least the number of points set out in Column 4 of the Table to this section opposite the population served by the drinking water system; and
(c) in the drinking water system’s distribution system, from at least the number of points set out in Column 5 of the Table to this section opposite the population served by the drinking water system.
(2) The samples required by subsection (1) must be taken during each of the following periods:
1. The period from December 15, 2007 to April 15, 2008 and the corresponding period in every subsequent 12-month period.
2. The period from June 15, 2008 to October 15, 2008 and the corresponding period in every subsequent 12-month period.
(3) Despite subsection (1), if the population served by a drinking water system is less than 100 and if the number of buildings served by the system is less than five, the sampling requirements set out in subsection (1) do not apply and instead, one sample per building must be taken from plumbing that serves a private residence within the building, during the periods described in subsection (2) and in accordance with subsection 15.1-6 (1), paragraphs 1 and 2 of subsection 15.1-6 (2) and subsections 15.1-7 (1), (3) and (4).
TABLE standard sampling — number of sampling locations
Column 1 Item | Column 2 Population Served by Drinking Water System | Column 3 Number of Sampling Points in Plumbing that Serves Private Residences | Column 4 Number of Sampling Points in Plumbing that Does Not Serve Private Residences | Column 5 Number of Sampling Points in Distribution System
1. | 1- 99 | 5 | 1 | 1
2. | 100 - 499 | 10 | 1 | 2
3. | 500 - 3,299 | 20 | 2 | 4
4. | 3,300 - 9,999 | 40 | 4 | 8
5. | 10,000 - 49,999 | 60 | 6 | 12
6. | 50,000 - 99,999 | 80 | 8 | 16
7. | 100,000 or more | 100 | 10 | 20
Reduced sampling
15.1-5. (1) Section 15.1-4 ceases to apply to a drinking water system, and this section applies instead, if,
(a) in the case of a system that serves a population of less than 50,000,
(i) in each of two consecutive periods described in subsection 15.1-4 (2),
(A) not more than 10 per cent of all the samples taken from plumbing under section 15.1-4 and tested for lead exceeded half the standard prescribed for lead, according to the results of the tests conducted under section 15.1-7, and
(B) no sample taken from plumbing under section 15.1-4 and tested for lead exceeded the standard prescribed for lead, according to the results of the tests conducted under section 15.1-7, or
(ii) in each of four consecutive periods described in subsection 15.1-4 (2), not more than 10 per cent of all the samples taken from plumbing under section 15.1-4 and tested for lead exceeded the standard prescribed for lead, according to the results of the tests conducted under section 15.1-7;
(b) in the case of a system that serves a population of 50,000 or more, in each of four consecutive periods described in subsection 15.1-4 (2), not more than 10 per cent of all the samples taken from plumbing under section 15.1-4 and tested for lead exceeded the standard prescribed for lead, according to the results of the tests conducted under section 15.1-7.
(2) For the purpose of subsection (1), if two samples that are taken on the same day from a point in plumbing are tested for lead under section 15.1-7, the sample with the lower concentration of lead shall not be considered.
(3) If a drinking water system serves a population of less than 50,000 and, under subsection (1), section 15.1-4 does not apply to the system, the owner of the drinking water system and the operating authority for the system shall ensure that, in accordance with sections 15.1-6 and 15.1-7, samples are taken during the periods described in subsection (5) in every third 12-month period after samples were last taken under section 15.1-4 or this section,
(a) in plumbing that serves private residences, from at least the number of points set out in Column 3 of the Table to this section opposite the population served by the drinking water system;
(b) in plumbing that does not serve private residences, from at least the number of points set out in Column 4 of the Table to this section opposite the population served by the drinking water system; and
(c) in the drinking water system’s distribution system, from at least the number of points set out in Column 5 of the Table to this section opposite the population served by the drinking water system.
(4) If a drinking water system serves a population of 50,000 or more and, under subsection (1), section 15.1-4 does not apply to the system, the owner of the drinking water system and the operating authority for the system shall ensure that, in accordance with sections 15.1-6 and 15.1-7, samples are taken during the periods described in subsection (5), in every 12-month period after samples were last taken under section 15.1-4 or this section,
(a) in plumbing that serves private residences, from at least the number of points set out in Column 3 of the Table to this section opposite the population served by the drinking water system;
(b) in plumbing that does not serve private residences, from at least the number of points set out in Column 4 of the Table to this section opposite the population served by the drinking water system; and
(c) in the drinking water system’s distribution system, from at least the number of points set out in Column 5 of the Table to this section opposite the population served by the drinking water system.
(5) The samples required by subsections (3) and (4) must be taken during each of the following periods in the relevant 12-month period:
1. The period from December 15 to April 15.
2. The period from June 15 to October 15.
(6) This section ceases to apply to a drinking water system, and section 15.1-4 applies again, if in any period described in subsection (5), more than 10 per cent of all the samples taken from plumbing under that subsection and tested for lead exceeded the standard prescribed for lead, according to the results of the tests conducted under section 15.1-7.
(7) For the purpose of subsection (6), if two samples that are taken on the same day from a point in plumbing are tested for lead under section 15.1-7, the sample with the lower concentration of lead shall not be considered.
(8) Despite subsection (3), if the population served by the drinking water system is less than 100 and if the number of buildings served by the system is less than five, the sampling requirements set out in subsection (3) do not apply and instead, one sample per building must be taken from plumbing that serves a private residence within the building, during the periods described in subsection (2) and in accordance with subsection 15.1-6 (1), paragraphs 1 and 2 of subsection 15.1-6 (2) and subsections 15.1-7 (1), (3) and (4).
(9) The requirements for taking samples set out in clauses (3) (a) and (b) and subsection (8) cease to apply to a drinking water system if, in each of two consecutive periods described in subsection (5) not more than 10 per cent of all the samples from plumbing taken under clause (3) (a) or (b) or subsection (8), or taken in accordance with a condition imposed under subsection 38 (2), 46 (2) or 60 (2) of the Act with respect to a system that serves a population of less than 50,000, that were tested for lead exceed the standard prescribed for lead, according to the results of the tests conducted under clause 15.1-7 (3) (a) or under a condition imposed under subsection 38 (2), 46 (2) or 60 (2) of the Act.
(10) When the requirements for taking samples set out in clauses (3) (a) and (b) and subsection (8) cease to apply under subsection (9) to a drinking water system, the owner of the drinking water system and the operating authority for the system shall ensure that samples are taken as described in clause (3) (c), in accordance with subsection 15.1-7 (2),
(a) to test for total alkalinity and for pH during each of the periods described in subsection (5) in every 12-month period; and
(b) to test for lead during each of the periods described in subsection (5) in every third 12-month period.
(11) The requirements for taking samples set out in clauses (3) (a) and (b) and subsection (8) apply to a drinking water system again if the Director provides a written direction to the owner or operating authority of the system that the requirements apply to the system.
(12) The Director shall not provide a written direction under subsection (11) unless the Director has knowledge of water chemistry changes in the water of the drinking water system and in the Director’s opinion the changes may increase levels of lead in the drinking water supplied by plumbing that is connected to the drinking water system.
TABLE reduced sampling — number of sampling locations
Column 1 Item | Column 2 Population Served by Drinking Water System | Column 3 Number of Sampling Points in Plumbing that Serves Private Residences | Column 4 Number of Sampling Points in Plumbing that Does Not Serve Private Residences | Column 5 Number of Sampling Points in Distribution System
1. | 1- 99 | 3 | 0 | 1
2. | 100 - 499 | 5 | 1 | 1
3. | 500 - 3,299 | 10 | 1 | 2
4. | 3,300 - 9,999 | 20 | 2 | 3
5. | 10,000 - 49,999 | 30 | 3 | 4
6. | 50,000 - 99,999 | 40 | 4 | 8
7. | 100,000 or more | 50 | 5 | 10
Selection of sampling points
15.1-6. (1) The owner of a drinking water system and the operating authority for the system shall ensure that a sample taken from plumbing under section 15.1-4 or 15.1-5 is taken only with the consent of the occupant of the premises served by the plumbing.
(2) In selecting points in plumbing from which samples are to be taken under section 15.1-4 or 15.1-5, the owner of the drinking water system and the operating authority for the system shall ensure that the samples comply with the following rules:
1. Subject to paragraph 2, samples must be taken from,
i. plumbing that is connected or is suspected of being connected to lead service pipes, or
ii. lead plumbing or plumbing that is suspected of being lead plumbing.
2. To the extent that it is not reasonably possible to take samples from plumbing described in paragraph 1, samples may be taken from,
i. plumbing that is connected or is suspected of being connected to service pipes that are not lead service pipes but have lead solder, or
ii. plumbing that is not lead plumbing but has or is suspected of having lead solder.
3. Samples must not be taken from more than one point in the same building, unless the number of buildings served by the drinking water system is less than the number of sampling points set out in Column 3 of the Table to section 15.1-4 opposite the population served by the drinking water system.
4. Subject to paragraphs 1 to 3, samples must be taken from plumbing that serves different kinds of premises, including,
i. single-family homes and multi-unit residential buildings, in the case of samples taken under clause 15.1-4 (1) (a) or 15.1-5 (3) (a) or (4) (a), and
ii. commercial properties, industrial properties, designated facilities and public facilities, in the case of samples taken under clause 15.1-4 (1) (b) or 15.1-5 (3) (b) or (4) (b).
5. Subject to paragraphs 1 to 3, samples must be taken from different geographical areas that are served by the drinking water system.
(3) The owner of a drinking water system and the operating authority for the system shall ensure that each sample taken from the system’s distribution system under section 15.1-4 or 15.1-5 is taken,
(a) on the same day that samples are taken from points in plumbing under that section; and
(b) from a point in the distribution system that is as close as reasonably possible to the points in plumbing from which samples are taken.
Sampling protocol and testing
15.1-7. (1) The owner of a drinking water system and the operating authority for the system shall ensure that samples taken from a point in plumbing under section 15.1-4 or 15.1-5 are taken in accordance with the following rules:
1. Two one-litre samples and the sample described in paragraph 12 must be taken.
2. All three samples must be taken from the same tap.
2.1 The samples must be of cold water.
3. If the tap from which samples are to be taken has an aerator, the aerator must not be removed while the samples are being taken.
4. The samples must be taken from,
i. a kitchen tap, if the sample is being taken from plumbing that serves premises that have a kitchen tap, or
ii. the tap that is most commonly used to provide water for human consumption, in any other case.
5. If a filter or other water-treating device is installed on or near the tap specified in paragraph 4, the filter or other device must be bypassed without being removed, if it is reasonably possible to do so, while the samples are being taken.
6. If a filter or other water-treating device is installed on or near the tap specified in paragraph 4 and it is not reasonably possible to bypass the filter or other device without removing it, the samples must be taken from another tap that is commonly used to provide water for human consumption.
7. If a filter or other water-treating device is installed on or near every tap that provides water for human consumption and, in every case, it is not reasonably possible to bypass the filter or other device without removing it, the samples must be taken from the tap specified in paragraph 4, but the filter or other device must be removed before the step described in paragraph 8 is taken.
8. Before the first sample is taken in accordance with paragraph 9, the tap must be turned on for at least five minutes and then turned off for the period described in subparagraph 9 i.
9. The first sample to be taken must be taken in accordance with the following rules:
i. The sample must be taken immediately after a period of not less than 30 minutes but not more than 35 minutes during which the plumbing is not used and must include the first water that comes out when the tap is turned on to take the sample.
ii. The sample must be taken with water flowing at a rate that approximates normal use, without permitting water to splash out of the container in which the sample is being collected.
10. The second sample to be taken must be taken immediately after the first sample, without turning off the tap or altering the flow rate of the tap.
11. Unless the laboratory directions referred to in section 6-8 of Schedule 6 provide otherwise, two or more containers may be used to take the first sample and to take the second sample, but in that case the time taken to switch from one container to the next must be kept to a minimum.
12. The third sample to be taken must be taken immediately after the second sample, without turning off the tap or altering the flow rate of the tap.
(2) The owner of a drinking water system and the operating authority for the system shall ensure that samples taken from a point in the system’s distribution system under section 15.1-4 or 15.1-5 are taken in accordance with the following rules:
1. Before the samples are taken, the point in the distribution system must be flushed until the quality of the water at the point is representative of the quality of the water in that part of the distribution system.
2. Three samples must be taken.
3. If a sample cannot be taken from a point in the system’s distribution system, a sample of cold water may be taken instead from a point in plumbing connected to the distribution system, provided that before the sample is taken the point is flushed until the quality of the water at the point is representative of the quality of water in the part of the distribution system that is connected to the plumbing.
4. Samples must not be taken from points in the distribution system where lead levels are likely to be elevated due to materials used in fixtures or appurtenances located at or near the sampling point.
(3) The owner of the drinking water system and the operating authority for the system shall ensure that,
(a) the samples taken under paragraphs 9 and 10 of subsection (1) and the first sample taken under subsection (2) are tested for lead;
(b) the second sample taken under subsection (2) is tested for total alkalinity; and
(c) the sample taken under paragraph 12 of subsection (1) and the third sample taken under subsection (2) are each tested for pH,
(i) immediately after the sample is taken, and
(ii) using a pH meter that measures pH to at least two significant digits.
(4) The owner of the drinking water system and the operating authority for the system shall ensure that samples are taken and pH tests are conducted under this section only by,
(a) a certified operator;
(b) a water quality analyst;
(c) a medical officer of health or public health inspector within the meaning of the Health Protection and Promotion Act;
(d) a trained person;
(e) a person who,
(i) has been trained by a certified operator to take samples and conduct pH tests in accordance with this section,
(ii) works under the supervision of a certified operator, and
(iii) advises a certified operator of all pH test results within a reasonable period of time; or
(f) an emergency substitute operator.
Drinking water tests
15.1-8. Every test of a sample taken from plumbing under section 15.1-4 or 15.1-5 is prescribed as a drinking water test for the purpose of the definition of “drinking water test” in section 2 of the Act.
Reporting requirements for samples taken from plumbing
15.1-9. (1) If the operating authority for a drinking water system or the owner of a drinking water system receives a report of a test result for a test conducted on any sample referred to in subsection (2.1), the operating authority or owner shall, within seven days after receiving the report, give the following to the occupant of the premises served by the tap from which the sample was taken and, if the sample was taken from a private residence within a multi-unit residential building, the owner of the building or their agent:
1. A copy of the report.
2. A statement of whether the report indicates a result that exceeds any Schedule 2 standard.
3. If the report indicates a result described in paragraph 2, any advice given by the medical officer of health to the operating authority or owner with respect to any steps that the occupant should take.
4. The telephone number of a person who is available to answer questions about the report.
(2) If a laboratory conducts a test of a sample referred to in subsection (2.1) and a result of the test exceeds any Schedule 2 standard, the laboratory shall, within 24 hours after the result is authorized pursuant to subsection 12 (1) or paragraph 4 of subsection 12.0.1 (3) of Ontario Regulation 248/03 (Drinking Water Testing Services) made under the Act, give a written report to,
(a) the operating authority for the drinking water system, if an operating authority is responsible for the system;
(b) the owner of the drinking water system, if no operating authority is responsible for the system;
(c) the medical officer of health; and
(d) the Ministry’s Spills Action Centre.
(2.1) The requirements set out in subsections (1) and (2) apply in respect of any sample taken from plumbing under subsection 15.1-4 (1) or (3) or subsection 15.1-5 (3), (4) or (8), in accordance with sections 15.1-6 and 15.1-7, whether or not the sample is taken in a period specified in subsection 15.1-4 (2) or 15.1-5 (5).
(3) The report required by subsection (2) shall specify,
(a) the result that requires the report; and
(b) the particular Schedule 2 standard that the result exceeds.
(4) If a laboratory reports a test result to the operating authority for a drinking water system under subsection (2), the operating authority shall, within 24 hours after receiving the report, give a copy of the report to the owner of the system.
(5) If a laboratory reports a test result to the operating authority for a drinking water system or the owner of a drinking water system under subsection (2), the operating authority or owner shall, within 24 hours after receiving the report, give a copy of the report to the medical officer of health.
(6) If a copy of a report is given to the operator of a designated facility under subsection (1), the operator shall provide a copy of the report to the interested authority for the facility, as soon as reasonably possible and preferably within 24 hours after the operator receives the copy.
(6.1) Revoked: O. Reg. 458/16, s. 13 (1).
(7) A written document that is given under subsection (2), (4), (5) or (6) may be delivered personally or sent by fax or by electronic mail.
(8) Despite subsection (7), the Ministry’s Spills Action Centre may require that a report that is given to the Centre under subsection (2) be given in an electronic format specified by the Director.
(9) Section 18 of the Act and Schedule 16 to this Regulation do not apply to a test of a sample taken from plumbing under section 15.1-4 or 15.1-5.
Corrective action for adverse results
15.1-10. If a report is made under subsection 15.1-9 (2), the owner of the drinking water system and the operating authority for the system shall take such steps as are directed by the medical officer of health, including, if directed by the medical officer of health, providing information to occupants of the premises served by the plumbing from which the sample was taken that is in addition to the information provided under paragraph 3 of subsection 15.1-9 (1).
Corrosion control
15.1-11. (1) This section applies to a large municipal residential system if,
(a) in two of the three most recent periods described in section 15.1-4 or 15.1-5, more than 10 per cent of all the samples taken from plumbing under that section and tested for lead exceed the standard prescribed for lead, according to the results of the tests conducted under section 15.1-7; and
(b) in each of the two periods mentioned in clause (a), the number of samples that exceed the standard prescribed for lead is at least two.
(2) For the purpose of subsection (1), if two samples that are taken on the same day from a point in plumbing are tested for lead under section 15.1-7, the sample with the lower concentration of lead shall not be considered.
(3) Within one year after the last day of the period mentioned in subsection (1) during which the test results are such as to cause this section to apply, the owner of the system and the operating authority for the system shall ensure that a plan that complies with subsection (5) is prepared and submitted to a Director appointed by the Minister under section 6 of the Act in respect of section 32 of the Act.
(4) The plan shall be prepared and submitted in a form and manner approved by the Director.
(5) The plan shall,
(a) analyze the potential for lead leaching into water as a result of corrosion that occurs in the system’s distribution system or in plumbing that is connected to the system’s distribution system;
(b) list and analyze possible measures to reduce the potential for lead leaching;
(c) identify the preferred measure or measures;
(d) set out an implementation schedule; and
(e) include a program for monitoring the effectiveness of the preferred measure or measures.
(6) If subsection (3) applies to a drinking water system that obtains treated water from another drinking water system,
(a) subsection (3) also applies to the owner of the other system and to the operating authority for the other system;
(b) the plan mentioned in subsection (3) shall be a joint plan; and
(c) the owner and operating authority mentioned in clause (a) shall, jointly with the owner of the system that obtains the treated water and the operating authority for that system, ensure that the plan is prepared and submitted.
(7) If the drinking water system referred to in clause (6) (a) itself obtains treated water from another system, subsection (6) also applies to that other system.
(8) If the plan mentioned in subsection (3) requires the owner or the operating authority to do anything in connection with implementing measures under the plan or monitoring their effectiveness, the owner shall, at the same time as the plan is submitted to the Director, apply to the Director to amend the system’s approval or municipal drinking water licence to reflect the requirements of the plan.
(9) If the Director has amended the system’s approval or municipal drinking water licence under subsection (8) and the owner or operating authority is carrying out the monitoring program described by clause (5) (e), the requirements for taking samples set out in subsection 15.1-4 (1), subsection 15.1-4 (3), subsections 15.1-5 (3) and (4) and subsection 15.1-5 (8) cease to apply to the drinking water system.
Non-municipal year-round residential system: certified operators
15.1-12 If, pursuant to subsection 2-11 (1) or (2) of Schedule 2, the owner of a non-municipal year-round residential system is not required to comply with provisions of that Schedule, a reference in this Schedule to a certified operator shall be deemed, with respect to that system, to be a reference to any person.
Read the drinking water systems on e-Laws ↗
Made under Safe Drinking Water Act, 2002, S.O. 2002, c. 32.