OPERATING ENGINEERS, O. Reg. 219/01
Section 45
Refrigeration plant installation requirements
Cite as OPERATING ENGINEERS, O. Reg. 219/01, s. 45 · current to November 11, 2026 · consolidated from June 27, 2001 · read from e-Laws on November 17, 2026
The text
(1) A guarded refrigeration plant or installation that is to be operated as set out in Table 6 shall be equipped with the system devices and controls referred to in sections 39 and 42, as the case requires. O. Reg. 219/01, s. 45 (1).
(2) A refrigeration installation referred to in subsection (1) shall be equipped with,
(a) an audible, visible alarm or remote pager system that, if any potentially unsafe condition is indicated by a protective device,
(i) gives a warning to the operating engineer, operator or other person who is located in the plant and is in charge of the installation, and
(ii) continues to give a warning until the potentially unsafe condition is rectified or the installation is safely shut down;
(b) an automatic control system that controls the installation when the operating engineer, operator or other person in charge of the installation leaves the controls of the installation;
(c) protective devices and controls, including pressure relief devices, required by Ontario Regulation 220/01 (Boilers and Pressure Vessels);
(d) fail-safe devices required by section 39 that shall, if a potentially unsafe condition occurs, interrupt the supply of energy to the prime movers of the refrigerant compressor and prevent the installation from restarting under automatic control or under remote control; and
(e) such other devices as are necessary to allow the installation to be operated safely. O. Reg. 219/01, s. 45 (2).
(3) A refrigeration installation referred to in subsection (1) that is located in a machinery room, as defined by CAN/CSA-B52, shall be equipped with a gas detector system that will activate the alarm system required by clause (2) (a) and start a mechanical ventilation system if there is a leak of refrigerant causing the airborne concentration of refrigerant to rise above the level value as defined by CAN/CSA-B52. O. Reg. 219/01, s. 45 (3).
(4) A refrigeration installation referred to in subsection (1) shall comply with CAN/CSA-B52 and shall be installed and operated so as to ensure public safety. O. Reg. 219/01, s. 45 (4).
Read the OPERATING ENGINEERS on e-Laws ↗
Made under Technical Standards and Safety Act, 2000, S.O. 2000, c. 16.