propane storage and handling, O. Reg. 211/01
Section 27
Filling plants and container refill centres
Cite as propane storage and handling, O. Reg. 211/01, s. 27 · current to November 11, 2026 · consolidated from July 1, 2015 · read from e-Laws on November 16, 2026
The text
(1) No person shall operate a container refill centre or filling plant, as defined in the code adoption document, unless the container refill centre or filling plant is licensed. O. Reg. 211/01, s. 27 (1).
(2) An application for a licence for a container refill centre or filling plant shall be made to the director. O. Reg. 211/01, s. 27 (2).
(3) An applicant shall,
(a) submit the application in the form published by the designated administrative authority;
(b) pay the fee set by the authority;
(c) provide a letter from the municipality where the container refill centre or filling plant is located indicating that the use of it for its intended purpose does not contravene the zoning by-laws of the municipality;
(d) subject to subsections (15) and (16), prepare and submit a legible plan in triplicate that shows,
(i) the location of each propane storage tank, cylinder storage facility, underground piping or tubing and other propane handling facilities within the container refill centre or filling plant,
(ii) the location of parking spaces designated by the applicant for tanker truck parking,
(iii) the distance from each propane storage tank and cylinder storage facility to the property lines of the centre or plant,
(iv) each building or structure located within 50 feet of a propane storage tank,
(v) the location of each site where flammable or combustible substances are stored,
(vi) the capacity in USWG of each propane storage tank within the centre or plant, and
(vii) any other relevant information requested by the director that is necessary to ensure that the installation is safe and complies with this Regulation; and
(e) submit a pre-installation site check sheet that confirms that the site complies with the code adoption document. O. Reg. 211/01, s. 27 (3); O. Reg. 440/08, s. 6.
(4) The director shall issue a licence to operate a container refill centre or filling plant to an applicant if,
(a) the applicant complies with subsection (3);
(b) the applicant pays the fee set by the designated administrative authority for any engineering services or inspection services provided in connection with the application; and
(c) the refill centre or filling plant complies with the code adoption document. O. Reg. 211/01, s. 27 (4).
(5) A holder of a licence to operate a container refill centre or filling plant shall not make a modification to it unless the holder has applied for and received the written permission of the director. O. Reg. 211/01, s. 27 (5).
(6) The director may give written permission under subsection (5) if the modification meets the requirements of this Regulation. O. Reg. 211/01, s. 27 (6).
(7) An applicant under subsection (5) shall,
(a) set out in the application all details of the modification proposed;
(b) provide a letter from the municipality under clause (3) (c) if the modification affects compliance with the municipality’s zoning by-laws; and
(c) provide a new plan under clause (3) (d) if the modification entails any changes to the plan previously provided under that clause or a predecessor of it. O. Reg. 211/01, s. 27 (7).
(8) No person shall operate a container refill centre or a filling plant if a modification to it is made without the director’s written permission. O. Reg. 211/01, s. 27 (8).
(9) A holder of a licence to operate a container refill centre or a filling plant shall ensure that each employee of the holder who handles propane, each person who is authorized to transfer propane to a container and each person to whom the holder issues an access code, card or key to dispense propane is trained,
(a) in the safe handling of propane, including the safe operation and use of propane dispensing equipment; and
(b) in the use of emergency shut-down switches, valves and procedures in respect of propane. O. Reg. 211/01, s. 27 (9).
(10) A licence to operate a container refill centre or a filling plant expires one year after the date of its issue. O. Reg. 211/01, s. 27 (10).
(11) A holder of a licence to operate a container refill centre or filling plant shall display the original or a copy of the licence such that it is readily visible at the business address set out on the licence. O. Reg. 211/01, s. 27 (11).
(12) An operator of a propane vehicle situated at a container refill centre or a filling plant shall ensure that the engine ignition of the vehicle is off during refuelling of the vehicle with propane. O. Reg. 211/01, s. 27 (12).
(13) While a propane vehicle is being refuelled with propane, no person shall knowingly have in his or her possession lighted smoking material or any other ignited substance within 10 feet of,
(a) the propane dispenser used to refuel the vehicle;
(b) the propane tank of the vehicle; or
(c) the propane fill point of the vehicle. O. Reg. 211/01, s. 27 (13).
(14) No person shall knowingly refuel a propane vehicle with propane if,
(a) the vehicle’s engine ignition is on;
(b) the main-burner or pilot light of a fuel-fired appliance on board the vehicle is on; or
(c) any lit smoking material or other ignited substance is within 10 feet of,
(i) the propane dispenser used to refuel the vehicle,
(ii) the propane container of the vehicle, or
(iii) the propane fill point of the vehicle. O. Reg. 211/01, s. 27 (14).
(15) An applicant may prepare plans and submit only one copy under subsection (3) (d) if,
(a) the plans are reviewed by a professional engineer, are stamped with the engineer’s seal and are signed by him or her;
(b) the professional engineer submits a written declaration to the director that the plans comply with the requirements of this Regulation; and
(c) the plans are kept at the facility at all times during its construction. O. Reg. 211/01, s. 27 (15).
(16) Upon the request of an inspector, an applicant under subsection (15) shall produce the plans for inspection within 72 hours of the request. O. Reg. 211/01, s. 27 (16).
Read the propane storage and handling on e-Laws ↗
Made under Technical Standards and Safety Act, 2000, S.O. 2000, c. 16.