propane storage and handling, O. Reg. 211/01
Section 19
Unacceptable condition – immediate hazard
Cite as propane storage and handling, O. Reg. 211/01, s. 19 · current to November 11, 2026 · consolidated from July 1, 2015 · read from e-Laws on November 16, 2026
The text
(1) In this section and in section 20,
“unacceptable condition” means,
(a) with respect to an appliance, container or work, that it is being used for a purpose other than that for which it was authorized,
(b) with respect to an appliance, container or work, that an alteration to it, by the addition of a device or attachment or in any other way, or any deterioration of it, is likely to impair its safe operation, or
(c) with respect to an appliance or work, that the condition of piping, tubing or hoses, the venting of products of combustion, the supply of air for combustion or the clearance from adjacent combustible matter is likely to impair its safe operation or does not meet the requirements of this Regulation or, where it was installed before this Regulation came into force, that it does not meet the requirements of the predecessor to this Regulation as it existed when the appliance or work was installed. O. Reg. 211/01, s. 19 (1).
(2) Where a distributor finds that an appliance or work is in an unacceptable condition and that it constitutes an immediate hazard, the distributor shall,
(a) immediately shut off the supply of propane to the appliance or work;
(b) promptly notify the user in writing of the unacceptable condition, including a direction that the appliance or work not be used until the condition is corrected; and
(c) affix a notice containing the information required under clause (b) to the appliance or work. O. Reg. 211/01, s. 19 (2).
(3) A user to whom notice has been given under subsection (2) shall not use the appliance or work or permit its use until the condition has been corrected and a distributor or certificate holder has determined on re-inspection that the condition has been corrected. O. Reg. 211/01, s. 19 (3).
(4) A holder of a certificate or ROT who finds that an unacceptable condition of an appliance or work constitutes an immediate hazard shall,
(a) immediately shut off the supply of propane to the appliance or work;
(b) promptly give oral notice of the actions taken under clause (a) to the propane distributor;
(c) promptly give a written notice to the user,
(i) describing the condition that constitutes the immediate hazard, and
(ii) that contains a statement indicating that the appliance or work shall not be used until the condition is corrected;
(d) within 14 days of finding the condition, give written notice of the condition to the distributor, including notice that the supply of propane has been shut off; and
(e) affix a notice containing the information required by clause (c) to the appliance or work. O. Reg. 211/01, s. 19 (4).
(5) No owner or user to whom a notice has been given under this section shall use the appliance or work or permit its use until the condition is corrected. O. Reg. 211/01, s. 19 (5).
Read the propane storage and handling on e-Laws ↗