General, N.B. Reg. 91-191

Section 70

Storage batteries

Cite as General, N.B. Reg. 91-191, s. 70 · current to June 30, 2026 · read from New Brunswick Acts and Regulations on November 16, 2026

The text

(1) An employer shall ensure that storage batteries that discharge flammable gases are electrically charged only in rooms or areas designed for that purpose. (2) An employer shall ensure that the room or area referred to in subsection (1) (a) is adequately ventilated to prevent the accumulation of flammable gases, (b) is free from all sources of ignition, (c) is marked at the entrance with a notice prohibiting smoking or open flames, (d) has a floor of non-sparking material with adequate drainage, (e) when storage batteries are mounted in trays or on racks, has level trays or racks constructed or covered with non-sparking material and of sufficient strength to carry the weight of the batteries, (f) has a sufficient supply of fresh water for flushing and neutralizing spilled or splashed electrolyte, (g) complies with Rules 26-500 to 26-514 of CSA standard C22.1-18, Canadian Electrical Code, Part 1, as amended, (h) has equipment of adequate capacity if equipment is used for hoisting or handling batteries, and (i) is not used for general storage. (3) An employer shall ensure that the floor in a storage battery room or area is washed promptly when electrolyte is spilled.
Read the General on the Province's website ↗

Made under Occupational Health and Safety Act, c. O-0.2.