General, N.B. Reg. 91-191
Section 342.3
Testing
Cite as General, N.B. Reg. 91-191, s. 342.3 · current to June 30, 2026 · read from New Brunswick Acts and Regulations on November 16, 2026
The text
(1) With respect to testing, an employer shall ensure that
(a) in the case of a commercially manufactured laboratory fume hood, the fume hood is certified as being tested by the manufacturer following its installation but prior to its first use, and
(b) in the case of a custom-built laboratory fume hood, the fume hood is tested on site by a competent person following its installation but prior to its first use.
(2) A laboratory fume hood tested under subsection (1) shall demonstrate containment not greater than the control level of 0.05 ppm when tested under "as manufactured" test conditions in accordance with the methods described in ANSI/ASHRAE Standard 110-1995, “Method of Testing Performance of Laboratory Fume Hoods” or a standard offering equivalent or better protection.
Read the General on the Province's website ↗
Made under Occupational Health and Safety Act, c. O-0.2.