General, N.B. Reg. 91-191
Section 342.2
Face velocities
Cite as General, N.B. Reg. 91-191, s. 342.2 · current to June 30, 2026 · read from New Brunswick Acts and Regulations on November 16, 2026
The text
An employer shall ensure that a laboratory fume hood meets the following requirements:
(a) the laboratory fume hood is connected to a local exhaust ventilation system;
(b) the average face velocity across the operational face opening of the laboratory fume hood is 0.4 m/s to 0.6 m/s;
(c) the face velocity is not less than 80% of the average face velocity required under paragraph (b) at any point across the operational face opening of the laboratory fume hood; and
(d) the face velocity is not more than 120% of the average face velocity required under paragraph (b) at any point across the operational face opening of the laboratory fume hood.
Read the General on the Province's website ↗
Made under Occupational Health and Safety Act, c. O-0.2.