General, N.B. Reg. 91-191

Section 289

Unqualified person and working distances from energized electrical utility line or utility line equipment

Cite as General, N.B. Reg. 91-191, s. 289 · current to June 30, 2026 · read from New Brunswick Acts and Regulations on November 16, 2026

The text

(1) An employer shall ensure that an employee who is not a qualified person does not carry out any work, and no such employee shall carry out any work, that is liable to bring any person or object closer to an energized electrical utility line or utility line equipment than the distances specified in the following table: Phase to Phase Voltage ofEnergized ElectricalUtility Line orUtility Line Equipment | Distance Up to 750 v | 900 mm 750 v - 100,000 v | 3.6 m 100,001 v - 250,000 v | 5.2 m 250,001 v - 345,000 v | 6.1 m (2) Where an employee who is not a qualified person is about to commence work that is liable to bring any person or object closer to an energized electrical utility line or utility line equipment than a distance specified in subsection (1), an employer shall contact the authority owning or operating the energized electrical utility line or utility line equipment and shall ensure that the utility line or utility line equipment (a) is de-energized, or (b) is adequately insulated or guarded before permitting the employee to commence the work.
Read the General on the Province's website ↗

Made under Occupational Health and Safety Act, c. O-0.2.