Section 287.5
Main service switches and temporary panel boards
Cite as General, N.B. Reg. 91-191, s. 287.5 · current to June 30, 2026 · read from New Brunswick Acts and Regulations on November 16, 2026
The text
An employer shall ensure that main service switches and temporary panel boards of electrical equipment
(a) are securely mounted on sufficient supports on an upright position,
(b) are kept clear of any obstructions for one metre in front and two metres headroom,
(c) are within easy reach of and readily accessible to authorized persons,
(d) are adequately protected from weather and the accumulation of water,
(e) have a suitable cover over uninsulated energized parts, and
(f) have a label or other indicator that identifies what equipment is energized by each line.
Read the General on the Province's website ↗
Made under Occupational Health and Safety Act, c. O-0.2.