MINIMUM STANDARDS FOR CASING
Cite as Water Well, N.B. Reg. 90-79, Schedule A · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026
The text
Metal Surface Casing
Metal surface casing shall conform to ASTM standard A589-84, Standard Specification for Seamless and Welded Carbon Steel Water-Well Pipe and meet the following minimum standards of wall thickness and weight:
Nominal size(inside diameter) | Wall Thickness | Nominal Weight Per Foot lbs. (Plain End)
12.70 cm | ( 5 in.) | 0.478 cm | (0.188 in.) | 10.8
15.24 cm | ( 6 in.) | 0.478 cm | (0.188 in.) | 12.9
17.78 cm | ( 7 in.) | 0.587 cm | (0.231 in.) | 16.7
20.32 cm | ( 8 in.) | 0.478 cm | (0.188 in.) | 16.9
22.86 cm | ( 9 in.) | 0.714 cm | (0.281 in.) | 28.0
25.40 cm | (10 in.) | 0.478 cm | (0.188 in.) | 21.2
1 Individual complete lengths of casing shall be between 4.5 m (15 ft.) and 7.2 m (22 ft.) long.
2 Galvanized casing is acceptable.
3 Minimum wall thickness shall be not more than 12 per cent under the normal wall thickness specified.
4 Outside diameter shall not vary more than ± 1 per cent from the size specified.
Other Materials Used As Casing
Plastic (ABS) pipe may be used for well casing if it is certified by and carries the marking of the Canadian Standards Association, indicating compliance with Canadian Standards Association Standard B181.1-1973, Acrylonitrile-Butadiene-Styrene Drain, Waste and Vent (ABS-DWV) Pipe and Pipe Fittings.
Other materials used must conform to Canadian Standards Association specifications for those materials when used as well casing.