Water Well, N.B. Reg. 90-79

Section 30

Cite as Water Well, N.B. Reg. 90-79, s. 30 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026

The text

If a pump is installed in a well, the person who installs the pump shall (a) except in the case of a dug well, seal the top of the well casing with a well cap commercially manufactured for the purpose, (b) disinfect the pump and the well using a method of disinfection approved by the Minister before installation of the pump, and (c) install an air vent that has an inside diameter of not less than six millimetres and that extends into the open air at least three hundred millimetres above the land surface at the opening of the well and the open end of which is shielded and screened to prevent the entry into the air vent of any substance which might impair the quality of the water in the well.
Read the Water Well on the Province's website ↗

Made under Clean Water Act, c. C-6.1.