Petroleum Product Storage and Handling, N.B. Reg. 87-97

Section 247

Cite as Petroleum Product Storage and Handling, N.B. Reg. 87-97, s. 247 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026

The text

(1) Subject to subsection (2), an underground storage tank that has been excavated shall not be reused for the storage of a petroleum product. (2) A storage tank may be reused for the storage of a petroleum product only after it has been refurbished and meets the requirements of CAN4-S603.1-M85, “Galvanic Corrosion Protection Systems For Steel Underground Tanks For Flammable And Combustible Liquids”, or CAN4-S615-M83, “Standard for Reinforced Plastic Underground Tanks For Petroleum Products”. (3) A storage tank referred to in subsection (2) shall not be reused until the owner of the tank has supplied the Minister with a certificate acceptable to the Minister that is signed by a licenced manufacturer of the same or similar tanks and certifies that the tank meets the requirements of subsection (2).
Read the Petroleum Product Storage and Handling on the Province's website ↗

Made under Clean Environment Act, c. C-6.