Subject to section 239, when an underground storage tank system is to be out of service for a period of more than one hundred and eighty days, the owner or the operator shall
(a) notify the Minister in writing within seven days after the system goes out of service, providing the following information:
(i) the name and mailing address of the owner,
(ii) the name and mailing address of the operator,
(iii) the location of the system, and
(iv) a description of the nature and quantity of the contents,
(b) where the storage tank contains a petroleum product, empty the tank, connected piping and dispensing facilities of the liquid,
(c) fill the storage tank, connected piping and dispensing facilities with at least one kilogram of dry ice for each five hundred litres of tank capacity or with an inert material acceptable to the Minister,
(d) where there is a possibility of high groundwater that could cause the storage tank to float, fill the storage tank with inert material that will prevent uplift,
(e) ensure that fill pipe covers and covers over openings to measure liquid levels, dispensing facilities and power controls are kept locked in the off position, and
(f) ensure that vent piping is kept open.
Read the Petroleum Product Storage and Handling on the Province's website ↗
Made under Clean Environment Act, c. C-6.