Petroleum Product Storage and Handling, N.B. Reg. 87-97
Section 213
Cite as Petroleum Product Storage and Handling, N.B. Reg. 87-97, s. 213 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026
The text
(1) A pump referred to in section 210 shall be securely anchored and protected against damage from vehicles.
(2) An emergency valve conforming to ULC-S620-M1980, “Standard For Valves For Flammable And Combustible Liquids” and incorporating a fusible element having a maximum temperature rating of seventy-one degrees Celsius shall be installed in the supply line so that the shear point of the valve is at a level not more than twenty-five millimetres below the base of the dispensing unit.
(3) An emergency valve required under subsection (2) shall close automatically in the event of severe impact to the dispensing unit.
(4) An emergency valve required under subsection (2) shall be maintained in operating condition and serviced at least once every twelve months.
(5) A remote pumping system shall be fitted with an automatic leak detection device on the pressure side of the system.
(6) A remote pumping system shall be fitted with a device that will indicate on the control console, where applicable, that the device is activated.
Read the Petroleum Product Storage and Handling on the Province's website ↗
Made under Clean Environment Act, c. C-6.