Petroleum Product Storage and Handling, N.B. Reg. 87-97

Section 208

Cite as Petroleum Product Storage and Handling, N.B. Reg. 87-97, s. 208 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026

The text

Where a storage tank at a marina is at an elevation above the dispensing unit, the storage tank outlet shall be equipped at the tank outlet with an electrically-operated solenoid valve that is normally closed and that is designed to open only when the apparatus is being operated, so as to prevent siphoning in the event of a rupture of the supply line to the dispensing unit while the dispensing unit is not activated.
Read the Petroleum Product Storage and Handling on the Province's website ↗

Made under Clean Environment Act, c. C-6.