Petroleum Product Storage and Handling, N.B. Reg. 87-97

Section 189

Cite as Petroleum Product Storage and Handling, N.B. Reg. 87-97, s. 189 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026

The text

(1) A hose nozzle valve through which a petroleum product having a flash point below sixty degrees Celsius is dispensed by a motorized dispensing unit into a vehicle tank shall conform to ULC-S620-M1980, “Standard For Valves For Flammable And Combustible Liquids” and shall be constructed so that the valve (a) can be kept open only by the continuous application of manual pressure, or (b) is equipped with a device at the nozzle that will (i) allow automatic dispensing, (ii) automatically shut off when the vehicle tank is filled, and (iii) shut off if the nozzle is dropped or falls from the fill pipe. (2) A dispensing nozzle at a self-service outlet or marina shall be an automatic closing type without a hold-open device and shall conform to ULC-S620-M1980, “Standard For Valves For Flammable And Combustible Liquids”. (3) A hose for equipment referred to in subsections (1) and (2) shall conform to CAN4-S612-M83, “Standard For Hose Materials For Conducting Flammable and Combustible Liquids”.
Read the Petroleum Product Storage and Handling on the Province's website ↗

Made under Clean Environment Act, c. C-6.