Petroleum Product Storage and Handling, N.B. Reg. 87-97
Section 149
Cite as Petroleum Product Storage and Handling, N.B. Reg. 87-97, s. 149 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026
The text
A piping system shall be considered to be leaking when
(a) a petroleum product is detected in the vicinity of the piping system, or
(b) the piping system has been tested in accordance with subsection 145(1) and the test indicates a liquid loss greater than 0.189 litres per hour.
Read the Petroleum Product Storage and Handling on the Province's website ↗
Made under Clean Environment Act, c. C-6.