Petroleum Product Storage and Handling, N.B. Reg. 87-97

Section 111

Cite as Petroleum Product Storage and Handling, N.B. Reg. 87-97, s. 111 · current to June 13, 2012 · read from New Brunswick Acts and Regulations on November 16, 2026

The text

(1) A vent pipe outlet from an underground storage tank containing a flammable liquid shall (a) be located outside buildings, and (b) extend vertically to (i) at least the height of the highest point in the delivery vehicle tank or at least three thousand five hundred millimetres above adjacent ground level, whichever is greater, where the tank is fitted with a tight fill adaptor on the fill pipe, or (ii) at least three thousand five hundred millimetres above the adjacent ground level or the top of the fill pipe, whichever is greater, where the tank is not fitted with a tight fill adaptor on the fill pipe. (2) Vent piping from an underground storage tank for a petroleum product shall not be obstructed by any device that may cause excessive back pressure. (3) Vent pipes from an underground storage tank for a combustible liquid may be fitted with return bends, coarse screens or other devices to minimize the entry of foreign material and shall extend two thousand millimetres above adjacent ground level. (4) Vent pipes from an underground storage tank for a flammable liquid shall not be fitted with return bends and may be fitted with rain caps or other devices to minimize the entry of foreign material.
Read the Petroleum Product Storage and Handling on the Province's website ↗

Made under Clean Environment Act, c. C-6.