(1) All elevator hoistway landing openings shall be provided with hoistway doors or gates.
(2) The distance between the hoistway side of a door or gate and the hoistway edge of the landing sill shall be not more than four inches.
(3) Every hoistway landing door shall guard the full height and width of the openings and be one of the following types:
(a) self-closing horizontally sliding or swinging, single or double section;
(b) manually operated vertically sliding counterweighted, single or double section; or
(c) manually operated vertically sliding bi-parting counter-balanced.
(4) Every hoistway landing gate shall guard the full width of the opening and, when in the closed position, shall extend downwardly from a height of not less than five feet six inches to the landing sill.
(5) The headroom clearance of a landing entrance opening shall be the same as the inside clear car height.
(6) Any opening in a hoistway landing gate shall reject a ball two inches in diameter.
(7) Every hoistway landing door shall be provided with a vision panel of clear wired glass not over six inches wide and eighty square inches in area.
(8) A hoistway landing door or gate shall be built to withstand a force of seventy-five pounds applied perpendicularly to it at any point without permanently deforming it or leaving its guides.
Read the Safety Code for Elevating Devices and Amusement Devices on the Province's website ↗
Made under Elevators and Lifts Act, c. E-6.