Hazardous Waste Regulation, B.C. Reg. 63/88

Section 9

Prevention of fire, explosion and accidental reactions

Cite as Hazardous Waste Regulation, B.C. Reg. 63/88, s. 9 · last amended July 1, 2026 · read from BC Laws on November 17, 2026

The text

(1) The owner of a hazardous waste facility must prevent the accidental ignition or reaction of ignitable or reactive waste by protecting such waste from sources of ignition or reaction such as open flames, smoking, grinding and welding, hot surfaces, frictional heat, static, electrical or mechanical sparks, spontaneous ignition from heat producing chemical reactions and radiant heat by means of (a) electrical spark grounding where the potential for static buildup exists, (b) suitable separation distances or a barrier with a minimum fire rating of 2 hours between the waste and ignition sources, and (c) a warning sign, legible from a distance of 10 m, reading "DANGER — IGNITABLE/REACTIVE HAZARDOUS WASTE, NO OPEN FLAMES, SMOKING OR SPARKS". (2) The owner of any indoor hazardous waste facility which manages reactive or ignitable hazardous waste must (a) provide and maintain a continuous 24 hour fire alarm system with (i) smoke sensing alarms, and (ii) heat sensing alarms, capable of automatically stopping any forced air ventilation systems in the facility and summoning a 24 hour external emergency response through (iii) a local fire department, (iv) a local response team, or (v) on site security staff who have immediate communication access to a local response agency, (b) provide and maintain a fire suppression system specified by the Fire Commissioner or a local assistant to the Fire Commissioner as defined in the Fire Services Act, or where not so specified provide and maintain (i) a permanent, automatic system which uses foam, inert gas or dry chemical, or (ii) one portable ABC rated fire extinguisher with a minimum 10 kg capacity for every 250 m2 of the facility's space, (c) provide and maintain sufficient aisle space between containers of hazardous waste to allow the unobstructed movement of persons, fire protection equipment, spill control equipment and decontamination equipment to any part of the facility, (d) design and construct the facility so that the walls, doors and floor are noncombustible with a minimum fire rating of 2 hours, and (e) ensure that any heat required for the facility is provided only by indirect means such as hot water, steam or electrical resistance and not by any device which uses an open flame within 10 m of where wastes are located, nor by any other device prohibited by the Fire Commissioner or a local assistant to the Fire Commissioner under the Fire Services Act. (3) The owner of a hazardous waste facility that treats, stores or disposes of ignitable or reactive waste must take precautions to prevent reactions which may do any of the following: (a) generate extreme heat or pressure, fire or explosions; (b) produce uncontrolled toxic mists, fumes, dusts or gases in sufficient quantities to threaten human health or the environment; (c) produce uncontrolled flammable fumes or gases in sufficient quantities to pose a risk of fire or explosion; (d) damage the structural integrity of the facility.
Read the Hazardous Waste Regulation on BC Laws ↗

Made under Environmental Management Act, SBC 2003, c. 53.