Hazardous Waste Regulation, B.C. Reg. 63/88
Section 17.1
Additional requirements for storage of PCB wastes
Cite as Hazardous Waste Regulation, B.C. Reg. 63/88, s. 17.1 · last amended July 1, 2026 · read from BC Laws on November 17, 2026
The text
(1) Notwithstanding section 2 (3) to (6) and (8), all storage facilities where
(a) 1.0 kilogram or more of PCBs,
(b) 100 litres or more of PCB liquid, or
(c) 100 kilograms or more of PCB solids
are stored must comply with sections 3 to 14, 16, 17 and this section.
(2) For the purpose of determining the quantity, volume or weight by which PCBs, PCB liquids or PCB solids exceed the amount specified in subsection (1), the total amounts stored at each location owned or controlled by the same owner or operator must be added together.
(3) The owner of a storage facility used to store PCB wastes must ensure that
(a) drums up to 205 litre capacity used for PCB solids
(i) Repealed. [B.C. Reg. 132/92, s. 12 (a).]
(ii) are made of 18 gauge steel or heavier,
(iii) have a securely attached, close fitting removable steel lid and a gasket of PCB resistant material, and
(iv) are painted to prevent rusting,
(b) drums up to 205 litre capacity used for PCB liquids
(i) Repealed. [B.C. Reg. 132/92, s. 12 (b).]
(ii) are made of 16 gauge steel for PCB liquids placed in storage or repackaged on or after April 1, 1992 and 18 gauge steel for PCB liquids placed in storage before April 1, 1992,
(iii) have a closed top that is fitted with 2 screw plug bungs, and
(iv) are painted to prevent rusting,
(c) all containers used for PCB wastes, and all PCB equipment except transformers on skids, must be placed on pallets or an alternate system of storage that allows for visual inspection for leaks and easy removal of the waste,
(d) drums of PCB wastes must not be stacked more than 2 drums high,
(e) containers of PCB wastes other than drums are not stacked unless the containers have been specifically designed for stacking and in such case that they are not stacked more than 2 containers high,
(f) an up-to-date inventory and site map indicating where all PCBs are stored at the facility and a fire safety plan acceptable to the local assistant to the fire commissioner
(i) are provided to a director,
(ii) are provided to the local assistant to the fire commissioner, and
(iii) are kept on site for inspection by an officer,
(g) capacitors containing 0.5 kilogram or more of chlorobiphenyls are labelled with either Environment Canada's serialized, black and white "CAUTION/ATTENTION PCB" label, measuring 76 mm by 76 mm, or a reasonable alternative, unless the capacitor was stored in a container before this section came into effect,
(h) electrical transformers, electromagnets and other equipment containing chlorobiphenyls in a concentration exceeding 1% by weight are labelled with either Environment Canada's serialized, black and white "ATTENTION PCB" label, measuring 150 mm by 150 mm, or a reasonable alternative,
(i) electrical transformers, electromagnets and other equipment containing chlorobiphenyls in a concentration exceeding 50 parts per million by weight but not greater than 1% by weight are labelled with either Environment Canada's "ATTENTION — Contaminated with PCBs" label, or a reasonable alternative,
(i.1) containers containing chlorobiphenyls in a concentration exceeding 1% by weight are labelled with either Environment Canada's "ATTENTION — PCB Waste" label, or a reasonable alternative,
(j) the floor or other surface of the storage site on which undrained PCB equipment or PCB liquids are stored, whether indoors or outdoors, must be constructed of steel, concrete or other durable material,
(k) where undrained PCB equipment or PCB liquids are stored on a floor or other surface of the storage site, whether indoors or outdoors, the floor or surface of the site must be provided with curbing or sides sufficient to contain
(i) in the case where a single item is being stored, 125% of the volume of the PCB liquid in the item, and
(ii) in the case where more than one item is being stored, the greater of twice the volume in the largest item or 25% of the volume of all the PCB liquids stored on the floor or surface,
(l) where the material of the floor or other surface of the storage site or the curbing or sides referred to in paragraph (k) are capable of absorbing PCBs, they are sealed with a durable PCB resistant coating,
(m) where undrained PCB equipment or PCB liquids are stored on a floor or other surface of the storage site, any existing floor drains, sumps or other openings in the floor are closed and sealed to prevent the escape of liquid,
(n) doors to storage sites, fencing and other security barriers enclosing storage sites are labelled with Environment Canada's non-serialized, black and white "ATTENTION PCB" label, measuring 150 mm by 150 mm, or a reasonable alternative.
(4) Repealed. [B.C. Reg. 132/92, s. 13.]
Read the Hazardous Waste Regulation on BC Laws ↗
Made under Environmental Management Act, SBC 2003, c. 53.