Performance Standards for Air Conditioning or
Refrigeration Equipment and Fire Extinguishing Equipment,
Recycling or Recovery and Recycling Devices 1 Devices for the recovery or recovery and recycling of an ozone depleting substance or other halocarbon designed to be used with the type of air conditioning or refrigeration equipment or fire extinguishing equipment listed in Column 1 of Table 1 must be capable of ensuring removal of the ozone depleting substance or other halocarbon from the equipment being serviced by reducing the system pressure, below atmosphere, to the level listed in Column 2 of Table 1 opposite the type of equipment if the device was purchased before January 1, 1994 or to the level listed in Column 3 if the device was purchased on or after January 1, 1994.
Table 1 Column 1 Column 2
(devices purchased
before January 1, 1994) Column 3
(devices purchased
after January 1, 1994) inches of mercury
(vacuum) micrometers
of mercury
(absolute
pressure) inches of mercury
(vacuum) micrometers
of mercury
(absolute
pressure) Very High Pressure Equipment(a) and HCFC-22 appliances
with a charge of less than 23 kilograms 0 760 000 0 760 000 High Pressure Equipment with a charge of less than 23 kilograms(b) 4 658 000 10 506 000 High Pressure Equipment with a charge of more than 23 kilograms(c) 4 658 000 15 379 000
Low pressure equipment(d) 25 125 000 29 23 000 (a) examples are CFC-13, 402, 407, 502, Halon 1211 and 1301; (b) examples are CFC-12, 114, 401A, 500, HFC-134a; (c) examples are CFC-12, 114, 401A, 500, HCFC-22; (d) examples are CFC-11, HCFC 123. 2 Devices for recovery or recovery and recycling intended for use with small appliances that contain an ozone depleting substance in their cooling systems such as household refrigerators, household freezers and water coolers, must recover a minimum of 90% of the refrigerant in the cooling system of the appliance or remove the refrigerant to a pressure of 506 000 micrometers of mercury (10 inches of mercury vacuum). Devices for recovery and recycling intended for use with small appliances that do not have an operational compressor must recover a minimum of 80% of the refrigerant in the cooling system of the appliance or remove the refrigerant to a pressure of 506 000 micrometers of mercury (10 inches of mercury vacuum).