Drilling and Production Regulation, B.C. Reg. 282/2010
Section 47
Fire prevention
Cite as Drilling and Production Regulation, B.C. Reg. 282/2010, s. 47 · last amended April 1, 2025 · read from BC Laws on November 17, 2026
The text
A permit holder must ensure all of the following:
(a) fires and fired equipment are located a safe distance from flammable liquids or potential sources of ignitable vapours so that there is no undue risk of fire or explosion;
(b) all fires for any purpose are safeguarded by sufficient mechanical or other means so that no hazard to surrounding property is created;
(c) flares and incinerators are located at least
(i) a safe distance from any energy resource road or other resource road,
(ii) 80 m from any other public road,
(iii) 100 m from any permanent building, installation or works that is not associated with an energy resource activity, and
(iv) 100 m from any place of public concourse;
(d) all facility piping is arranged and provided with control valves to permit ready shut off of oil or gas in the event of fire at any facility installation;
(e) a separator is not enclosed within the fire wall, dike or ditch surrounding a storage tank installation, unless the installation is equipped with safety equipment designed to prevent fire, explosions or exposure of personnel to hydrogen sulphide or other toxic or poisonous gases;
(f) all vessels and equipment from which ignitable vapours may issue are safely vented to the atmosphere;
(g) explosives of every kind and description are stored only in properly constructed magazines, situated not less than 150 m from any place where any drilling, production or processing operation is being undertaken;
(h) a sufficient area beneath and around the flare stack is free of combustible materials and vegetation.
Read the Drilling and Production Regulation on BC Laws ↗
Made under Energy Resource Activities Act, SBC 2008, c. 36.