Energy Efficiency Standards Regulation, B.C. Reg. 14/2015
Section 49
Nominal full load efficiency for type 2 general purpose electric motors
Cite as Energy Efficiency Standards Regulation, B.C. Reg. 14/2015, s. 49 · last amended April 24, 2023 · read from BC Laws on November 17, 2026
The text
For the purposes of the efficiency standard referred to in column 4 in item 2 of the efficiency standards table in section 47 [efficiency standards for general purpose electric motors], the following table sets out the nominal full load efficiency for type 2 general purpose electric motors: Motor Efficiency (%) Column 1
Rated Power Column 2
Open Motors Number of Poles Column 3
Enclosed Motors Number of Poles (hp) (kW) 2 4 6 2 4 6 1 0.75 77.0 85.5 82.5 77.0 85.5 82.5 1.5 1.1 84.0 86.5 86.5 84.0 86.5 87.5 2 1.5 85.5 86.5 87.5 85.5 86.5 88.5 3 2.2 85.5 89.5 88.5 86.5 89.5 89.5 - 3.0 86.5 89.5 89.5 88.5 89.5 89.5 5 3.7 86.5 89.5 89.5 88.5 89.5 89.5 - 4.0 86.5 89.5 89.5 88.5 89.5 89.5 7.5 5.5 88.5 91.0 90.2 89.5 91.7 91.0 10 7.5 89.5 91.7 91.7 90.2 91.7 91.0 15 11 90.2 93.0 91.7 91.0 92.4 91.7 20 15 91.0 93.0 92.4 91.0 93.0 91.7 25 19 91.7 93.6 93.0 91.7 93.6 93.0 30 22 91.7 94.1 93.6 91.7 93.6 93.0 40 30 92.4 94.1 94.1 92.4 94.1 94.1 50 37 93.0 94.5 94.1 93.0 94.5 94.1 60 45 93.6 95.0 94.5 93.6 95.0 94.5 75 55 93.6 95.0 94.5 93.6 95.4 94.5 100 75 93.6 95.4 95.0 94.1 95.4 95.0 125 90 94.1 95.4 95.0 95.0 95.4 95.0 150 110 94.1 95.8 95.4 95.0 95.8 95.8 - 132 95.0 95.8 95.4 95.4 96.2 95.8 200 150 95.0 95.8 95.4 95.4 96.2 95.8
Read the Energy Efficiency Standards Regulation on BC Laws ↗
Made under Energy Efficiency Act, RSBC 1996, c. 114.