Liquefied Natural Gas Facility Regulation, B.C. Reg. 146/2014
Section 17
Venting
Cite as Liquefied Natural Gas Facility Regulation, B.C. Reg. 146/2014, s. 17 · last amended April 1, 2025 · read from BC Laws on November 17, 2026
The text
(1) An LNG facility permit holder must not vent gas from an LNG facility unless the gas heating value, volume or flow rate is insufficient to support stable combustion and all of the following apply:
(a) the venting is conducted in a manner that does not constitute a safety hazard;
(b) the venting does not cause off-site odours;
(c) the quantity of vented gas is minimized;
(d) the duration of venting is minimized.
(2) An LNG facility permit holder may use gas containing hydrogen sulphide for pneumatic instrumentation or to provide motive force to pumps only if the gas contains no more than 20 parts per million of hydrogen sulphide.