(1) Every manned offshore installation shall be equipped with a fire or gas detection system that includes
(a) one or more fire and gas detector indicator panels located at the control station, that
(i) indicate the source of fire and gas by means of a visual signal,
(ii) are capable of being functionally tested, and
(iii) are fitted with equipment for resetting the fire and gas detection systems; and
(b) an audible fire and gas alarm that has a characteristic tone that distinguishes it from the alarms associated with machinery, safety and control system faults or any other alarm system and that is audible on all parts of the installation.
(2) A fire or gas detection system referred to in subsection (1) shall
(a) be capable of being manually activated from each of the following locations, namely,
(i) the space adjacent to each entrance to each machinery and process space,
(ii) each accommodation area,
(iii) the office of the manager of the installation,
(iv) every control point in each machinery and process space, and
(v) the control station;
(b) be designed so that, on activation of a detection device in one space, any signals received at the same time from a detection device in another space will register at the fire and gas indicator panel at that same time;
(c) be installed and maintained in accordance with National Fire Prevention Association 72, Standard for the Installation, Maintenance, and Use of Protective Signaling Systems; and
(d) be arranged so that there will be an automatic changeover to an emergency source of electrical power in accordance with subsection 12(9) in the event of a failure of the primary source of electrical power and so that failure of the primary source of electrical power will be indicated both visually and audibly as a separate fault alarm.