Canada Oil and Gas Installations Regulations, SOR/96-118
Section 30
Cite as Canada Oil and Gas Installations Regulations, SOR/96-118, s. 30 · current to July 24, 2025 · regulation last amended October 6, 2020
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) Every manned offshore installation shall be provided with at least ten sets of firefighter equipment and every unmanned offshore installation shall be provided with at least two sets of firefighter equipment, each of which shall consist of
(a) protective clothing, including boots and gloves, that
(i) meets the requirements of National Fire Protection Association 1971, Standard on Protective Clothing for Structural Fire Fighting,
(ii) will protect the skin from being burned by heat radiating from a fire and by steam,
(iii) has a water-resistant outer surface,
(iv) in the case of boots, is made of rubber or other electrically non-conducting material, and
(v) in the case of gloves, meets the requirements of National Fire Protection Association 1973, Standard on Gloves for Structural Fire Fighting; and
(b) a firefighter’s helmet with visor that meets the requirements of Canadian Standards Association CAN/CSA-Z94.1-92, Industrial Protective Headwear.
(2) In addition to any firefighting equipment required by the Oil and Gas Occupational Safety and Health Regulations, every manned offshore installation shall be provided with at least four sets, and every unmanned offshore installation shall be provided with at least two sets, of the following equipment:
(a) a self-contained breathing apparatus that
(i) is capable of functioning for at least 30 minutes,
(ii) meets the requirements of Canadian Standards Association CAN/CSA-Z94.4-93, Selection, Use, and Care of Respirators, and CAN3-Z 180.1-M85, Compressed Breathing Air and Systems, and
(iii) is equipped with two spare bottles;
(b) a portable electric safety lamp that
(i) will operate in the conditions anticipated for a Class I, Division 1, hazardous area,
(ii) is operated from a rechargeable battery capable of operating for at least 3 hours, and
(iii) can be easily attached to the clothing of a firefighter, at or above the waist level;
(c) an axe with an insulated handle and a carrying belt; and
(d) a fire-resistant life and signalling line and a safety belt and harness that meet the requirements of National Fire Protection Association 1983, Standard on Fire Service Life Safety Rope, Harness and Hardware.
(3) Each set of equipment required by subsections (1) and (2) shall be kept ready for use and stored so as to be readily accessible.
(4) One of each of the sets of equipment required by subsections (1) and (2) shall be located within easy access of the helicopter deck.
Read the Canada Oil and Gas Installations Regulations on the Justice Laws Website ↗
Made under Canada Oil and Gas Operations Act, R.S.C. 1985, c. O-7.
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.