The text

(1) A water supply system for fire protection shall be installed along the side of every conveyor that is in service at a coal mine. (2) The flow pressure of the water in the system referred to in subsection (1) at any hydrant on the circuit shall be (a) not less than 340 kPa when two of the hydrants on that circuit are discharging water at a rate of 200 L/min; and (b) measured at a nozzle of 16 mm diameter that is attached to the hydrant.
Read the Coal Mining Occupational Health and Safety Regulations on the Justice Laws Website ↗

Made under Canada Labour Code, R.S.C. 1985, c. L-2.