Oil and Gas Occupational Safety and Health Regulations, SOR/87-612

Section 6.10

Cite as Oil and Gas Occupational Safety and Health Regulations, SOR/87-612, s. 6.10 · current to February 4, 2026 · regulation last amended January 30, 2026

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) Where more than five years have elapsed since the date of the last test and inspection of a Halon container, the container shall not be recharged without a test of container strength and a complete visual inspection being carried out. (2) A Halon container that has been continuously in service without being discharged may be retained in service for a maximum of 20 years after the date of the last test and inspection, at which time it shall be emptied, subjected to a test of container strength and a complete visual inspection and re-marked before being placed back in service. (3) Where a Halon container has been subjected to unusual corrosion, shock or vibration, a complete visual inspection and a test of container strength shall be carried out.
Read the Oil and Gas Occupational Safety and Health Regulations on the Justice Laws Website ↗

Made under Canada Labour Code, R.S.C. 1985, c. L-2.

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.