Canada Occupational Health and Safety Regulations, SOR/86-304

Section 9.41

Cite as Canada Occupational Health and Safety Regulations, SOR/86-304, s. 9.41 · current to February 18, 2026 · regulation last amended March 26, 2025

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) Each personal service room and food preparation area shall be ventilated to provide at least two changes of air per hour (a) by mechanical means, where the room is normally used by 10 or more employees at any one time; or (b) by mechanical means or natural ventilation through a window or similar opening, where the room is used by fewer than 10 employees if (i) the window or similar opening is located on an outside wall of the room, and (ii) not less than 0.2 m2 of unobstructed ventilation is provided for each of the employees who normally use the room at any one time. (2) Where an employer provides ventilation by mechanical means in accordance with paragraph (1)(a), the amount of air provided for a type of room set out in Column I of an item of the schedule to this Part shall be not less than that set out in Column II of that item. (3) Where an employer provides for the ventilation of a food preparation area or a lunch room by mechanical means in accordance with paragraph (1)(a), the rate of change of air shall be not less than nine litres per second for each employee who is normally employed in the food preparation area at any one time or for each employee who uses the lunch room at any one time.
Read the Canada Occupational Health and Safety Regulations on the Justice Laws Website ↗

Made under Canada Labour Code, R.S.C. 1985, c. L-2.

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.