Canada Occupational Health and Safety Regulations, SOR/86-304

Section 5.5

Cite as Canada Occupational Health and Safety Regulations, SOR/86-304, s. 5.5 · current to February 18, 2026 · regulation last amended March 26, 2025

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) An employer shall ensure that a qualified person, charged with the operation of a boiler, is in attendance and readily available at all times while the boiler is in operation and other employees are normally present in the same building as a boiler. (2) The attendance referred to in subsection (1) is not required if (a) the boiler is equipped with a fail-safe device and an automated warning device that will ensure the safe operation of the boiler and its shutdown if required, and that are installed in such a manner that they (i) cannot be rendered inoperative, and (ii) can be tested under operating conditions; and (b) the boiler is rated below 2,000 kW in the case of a high pressure boiler, and below 3,000 kW in the case of a low pressure boiler, which includes a low pressure hot water boiler, a low pressure organic fluid boiler and a low pressure steam boiler. (3) When a boiler is shut down by a device referred to in paragraph (2)(a), the boiler shall not be restarted unless it has been examined by a qualified person and the cause of the shutdown rectified.
Read the Canada Occupational Health and Safety Regulations on the Justice Laws Website ↗

Made under Canada Labour Code, R.S.C. 1985, c. L-2.