The text

(1) Every guardrail shall be highly visible and consist of (a) a horizontal top rail not less than 900 mm but not more than 1 100 mm above the base of the guardrail; (b) a horizontal intermediate rail spaced midway between the top rail and the base; and (c) supporting posts spaced not more than 3 m apart at their centres. (2) Every guardrail shall be designed to withstand a static load of 890 N applied in any direction at any point on the top rail.
Read the Canada Occupational Health and Safety Regulations on the Justice Laws Website ↗

Made under Canada Labour Code, R.S.C. 1985, c. L-2.